產(chǎn)品中心
Home > Product > Outdoor High Voltage Vacuum Circuit Breaker > LW16-40.5 Outdoor Sulfur Hexafluoride Circuit Breaker

    LW16-40.5 Outdoor Sulfur Hexafluoride Circuit Breaker

    LW16-40.5 outdoor sulfur hexafluoride circuit breaker is an outdoor device used in AC 50Hz three-phase power system for control and protection of industrial and mining enterprises, power plants and substations. This product can be operated frequently and can be used as a connecting circuit breaker and a circuit breaker for capacitor banks and reactor groups.
  • Category:
    Outdoor High Voltage Vacuum Circuit Breaker
  • Browse number:
    27
  • Release time:
    2024-09-21 23:41:23
  • Share:
  • INQUIRY

Overview

LW16-40.5 outdoor sulfur hexafluoride circuit breaker is an outdoor device used in AC 50Hz three-phase power systems for control and protection of industrial and mining enterprises, power plants and substations. This product can be operated frequently and can be used as a connecting circuit breaker and a circuit breaker for connecting capacitor banks and reactor groups. The built-in Current Transformer can be used for measurement and protection. It can directly replace the SW2-35 low-oil circuit breaker. It can replace various types of high-oil Circuit breakers with overcurrent brackets. It is an ideal oil-free circuit breaker in 35kV power systems.


Note: When the circuit breaker is in hot standby mode, a Lightning Arrester must be installed on the road side of the break.


Working conditions and use environment

1. Altitude: not more than 3000m;

2. Ambient temperature: -25℃~+40℃;

3. Wind speed: not more than 34m/s;

4. Pollution level IV, creepage distance of porcelain sleeve: > 1255mm;

5. Places without flammable substances, explosion hazards, chemical corrosion and severe vibration.

Note: If the above requirements are exceeded, the user can negotiate with the manufacturer.


Technical Parameters

NO.

Items name

Unit

Data

1

rated voltage

kV

40.5

2

rated insulation level

1-minute power frequency withstand voltage

kV

95

Lightning impulse withstand voltage

kV

185

3

Rated frequency

Hz

50

4

Rated current

A

1600, 2000

5

Rated short-circuit breaking current

kA

25 (reclosing), 31.5 (single-break)

6

Rated short-circuit making current (peak value)

kA

63

7

Rated short-time withstand current

kA

25

8

Rated short-circuit duration

S

4

9

Rated peak withstand current

kA

63

10

Rated operation sequence


O-0.3s-CO-180s-CO

11

Rated breaking current of single capacitor bank

A

400

12

Rated out-of-step breaking current

KA

6.3

13

Rated out-of-phase breaking current

kA

21.75

14

Mechanical life test

times

3000

15

Accumulated breaking times of rated current

times

2000

16

Rated short-circuit breaking current (25kA) cumulative breaking times

times

21

17

Opening time

Under rated or maximum operating voltage

s

≤0.06

At the minimum operating voltage

s

≤0.10

18

Closing time

s

≤0.15

19

Rated pressure of SF6 gas (gauge pressure at 20℃)

MPa

0.60±0.015

20

SF6 gas replenishment alarm pressure (gauge pressure at 20℃)

MPa

0.55 ±0.015

21

Minimum functional pressure of SF6 gas (gauge pressure at 20℃)

Mpa

0.S2±0.01S

22

annual leakage rate of SF6 gas

%/year

≤1

23

SF6 gas trace moisture content

V/V

≤150X10-6

24

CT14 A mechanism division

rated voltage of closing coil

AC

V

220

DC

V

110, 220

25

CT14-A mechanism energy storage

Rated voltage of electric motor

AC

V

220, 380

DC

V

110, 220

26

Weight of SF6 gas

kg

Normal: 2.5, with CT: 6, extra high with CT: 8

27

weight of circuit breaker

kg

1000

28

External insulation leakage ratio of circuit breaker

mm/kV

≥31

29

Porcelain bushing leakage distance

mm

≥1255


Technical Parameters

NO.

Items name

Unit

Data

1

Conductive rod stroke

mm

65±2

2

Dimension A from the upper end of the conductive rod at the closing position to the upper end of the porcelain bottle flange

mm

233

3

Minimum air insulation distance

mm

four hundred and forty

4

three-pole opening synchronism

ms

2

5

main circuit resistance

A

Normal 40 with CT 60

6

Initial sub-speed (under rated voltage)

m/s

2.4±0.2

7

Closing speed (under rated voltage)

m/s

2


Installation Dimensions


Related tags:

Comment

(0)
*Captcha:

ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Address:
*Captcha:
Contact us

Manager Zhou

Leave a message
Contact Now
Recommend

RELATED PRODUCTS

No search results found!
Follow us:

Oil&Gas exploited

Automotive Manufacturing

Transportation & Dlistrlbutlon

Manufacture

Industrial Construction

Green Energy

About US

Contact US

The news

Terms & conditions

Case Studies

Site map

Copyright ? 2024  All Rights Reserved

Back to top