產(chǎn)品中心
Home > Product > Outdoor High Voltage Vacuum Circuit Breaker > GFLW-12/24/40.5 Series Of Pole Mounted SF6 Load Break Switch

    GFLW-12/24/40.5 Series Of Pole Mounted SF6 Load Break Switch

    GFLW-12/24/40.5 series of pole-mounted SF6 load-break switches are used in power distribution networks with rated voltages of 12/24/40.5kV, rated currents of 400A or 630A ,and a rated frequency of 50/60Hz,to break and close the load current and overload current of the system, it can automatically isolate the faulty sections of the power distribution line.
  • Category:
    Outdoor High Voltage Vacuum Circuit Breaker
  • Browse number:
    32
  • Release time:
    2024-09-23 01:56:10
  • Share:
  • INQUIRY

Description

GFLW - 12/24/40.5 series of pole - mounted SF6 load - break switches are used in power distribution networks with rated voltages of 12/24/40.5kV, rated currents of 400A or 630A, and a rated frequency of 50/60Hz. They are used to break and close the load current and overload current, and can automatically isolate the faulty sections of the power distribution line.


The switch is matched with an electronic controller with the latest technology. It supports manual, motor - driven and remote operation modes. This electronic controller is installed inside a stainless - steel box, so it can be used in various climate conditions.


Besides, a wired and wireless modem is installed inside the control box, enabling it to realize remote monitoring and control. The switch is easy and convenient to install on the pole, which can reduce the construction cost.

Environment conditions

-Ambient temperature: max.+50°C  min.-40°C

- Altitude: not mare than 1000m(could also be 2000m, 3500m, 5000m as requested)

- Wind pressure: not mare than 700Pa(equals to wind speed 34m/s)

-Relative humidity:not more than100%

-Air contamination degree: Class IV 

-Earthquake intensity: ≤8 degree

- Not bepolluted by corrosive or flammable gas

- No frequent violent vibrationor explosive place


Technical Data

ModelGFLW-12GFLW-24GFLW-40.5
Ratedvoltage12KV24kV40.5kV
Rated current630A630A630A
Rated frequency50/60Hz50/60Hz50/60Hz
Short time withstand current20kA/1sec20kA/1sec20kA/1sec
Making and Breaking Capacity
Main Active Load Current630A630A630A
Number of Load-break Operations400 Times400 Times400 Times
Short-timeMaking Current (peak)50kA50kA50kA
Numberof MakingCurrentOperations5 Times5 Times5 Times
Cable Charging Current25A25A25A
Line Charging Current1.5A1.5A1.5A
Closed Loop Circuit Current630A630A630A
Transformer Magnetizing Current22A22A22A
Power Frequency Withstand VoltageTest
Wet Condition-10secPhase toPhase, Phase to Earth, Across Interrupters45kV50kV70kV
DryCondition-1minPhase toPhase,Phase to Earth50kV64kV95kV
Dry Condition - 1 min AcrossInterrupters50kV79kV110kV
Impulse Withstand VoltageTest(1.2 x 50 μs)
Phase to Earth85kV125kV195kV
Across Interrupter95kV145kV215kV
Other Ratings & Specifications
Internal Arc Test20kA /0.1 sec20kA /0.1 sec20kA /0.1 sec
Arc Extinction MediumSF 6 GasSF 6 GasSF 6 Gas
Insulation MediumSF 6 GasSF 6 GasSF 6 Gas
Creepage Distance (PorcelainBushing)380mm700mm1055mm
Creepage Distance (Silicone Rubber Bushing)540mm700mmmm
IP Level656565
Mechanical Performance
Closing/Opening Time<1sec<1sec<1sec
Mechanical Operations (Guaranteed)10000 Times10000 Times10000 Times
Operating Temperature (Manual Type)-25~+70℃-25~+70℃-25~+70℃
Gas Pressure
Nominal Pressure (MPa, at 20°C)0.070.070.07
ExplosionPressure (MPa)0.4~0.60.4~0.60.4~0.6
Minimum Gas Pressure (MPa)0.050.050.05
Gas Leakage Rate (cc/ sec)≤0.5%≤0.5%≤0.5%


Outline Dimension


Dimension (mm)Mounting Size (mm)Bushing creepage Distance (mm)Packing Size (mm)Weight (KGS)

ABCDL×W
L×W×H
12KV2255008031056500 × 125 (390)500 × 125 (390)1100 × 900 × 700105
24KV3006509531250500 × 125 (390)500 × 125 (390)1300 × 1100 × 700145
40.5KV40085011531380700 × 125 (390)700 × 125 (390)1400 × 1200 × 700165


Related tags:

Comment

(0)
*Captcha:

ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Address:
*Captcha:
Contact us

Manager Zhou

Leave a message
Contact Now
Recommend

RELATED PRODUCTS

No search results found!
Follow us:

Oil&Gas exploited

Automotive Manufacturing

Transportation & Dlistrlbutlon

Manufacture

Industrial Construction

Green Energy

About US

Contact US

The news

Terms & conditions

Case Studies

Site map

Copyright ? 2024  All Rights Reserved