產(chǎn)品中心
Home > Product > Outdoor High Voltage Vacuum Circuit Breaker > ZW□-40.5 Outdoor Sealed Permanent Magnet Circuit Breaker

    ZW□-40.5 Outdoor Sealed Permanent Magnet Circuit Breaker

    ZW□--40.5M outdoor high-voltage permanent magnetic vacuum circuit breaker adopts a specially designed integrated solid-sealed column and a highly reliable operating mechanism. This device is mainly used in medium-voltage overhead line power grids to disconnect and connect load current, overload current, and short-circuit current.
  • Category:
    Outdoor High Voltage Vacuum Circuit Breaker
  • Browse number:
    26
  • Release time:
    2024-09-21 23:25:25
  • Share:
  • INQUIRY

Overview

ZW□--40.5M outdoor high-voltage permanent magnetic vacuum circuit breaker adopts a designed integrated solid-sealed column and a highly reliable operating mechanism. The device is mainly used in medium-voltage overhead line power grids to disconnect and connect load current, overload current, and short-circuit current.

High reliability

Maintenance-free throughout the life cycle

High mechanical and electrical life

The whole machine is small in size, light in weight, and easy to install


Normal use conditions

Ambient air temperature: -30℃~+60℃;

Altitude: not more than 3000 meters;

Wind speed not more than 34m/s;

Vibration or earthquake from outside the switchgear and control equipment is negligible;

Pollution level: Level IV;

Storage temperature -40℃~+85℃.


Technical Parameters

NO.

Items

Unit

Date

1

rated voltage

kV

40.5

2

Rated current

A

1250/1600

3

Rated frequency

Hz

50 or 60

4

Power frequency withstand voltage for 1 minute (wet) (dry)

Interphase, ground/fracture

kV

80 95/95

5

Lightning impulse withstand current (peak value)

Interphase, ground/fracture

kV

185

6

Rated short circuit breaking current

kA

25/31.5

7

Rated short-circuit closing current (peak)

kA

63/80

8

Rated peak withstand current

kA

63/80

9

4S short-time withstand current

kA

25/31.5

10

Rated operating cycle


O0.1sCO3sCO-6sCO-60s Recovery

11

Rated short-circuit current breaking times

30

12

mechanical life

100000

13

Institutional control voltage

V

AC/DC220

14

Secondary circuit 1-minute power frequency withstand voltage

KV

2


Main mechanical parameters of circuit breaker

NO.

Parameter

Unit

Date

1

clearance between open contacts

mm

16±1

2

Contact overtravel

mm

4±0.5

3

opening speed

m/s

1.4-1.8

4

closing speed

m/s

0.4-0.8

5

Contact closing bounce time

ms

≤5

6

Center distance between phases

mm

600±2

7

Three phase opening and closing asynchrony

ms

≤2

8

Resistance of each phase conductive circuit

μΩ

80

9

close time

ms

2545

10

Opening time

ms

2045

11

weight

Kg

450


Related tags:

Comment

(0)
*Captcha:

ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Address:
*Captcha:
Contact us

Manager Zhou

Leave a message
Contact Now
Recommend

RELATED PRODUCTS

No search results found!
Follow us:

Oil&Gas exploited

Automotive Manufacturing

Transportation & Dlistrlbutlon

Manufacture

Industrial Construction

Green Energy

About US

Contact US

The news

Terms & conditions

Case Studies

Site map

Copyright ? 2024  All Rights Reserved

Back to top