Home > Product > Outdoor High Voltage Vacuum Circuit Breaker > LW36-72.5 126 Outdoor High Voltage Vacuum Circuit Breaker

    LW36-72.5 126 Outdoor High Voltage Vacuum Circuit Breaker

    72.5kV outdoor high voltage vacuum circuit breaker is designed for harsh environment, using fully sealed stainless steel housing and vacuum arc extinguishing technology, with explosion-proof, anti-corrosion, anti-ultraviolet performance, adapt to -40℃ to +40℃ extreme temperature. Rated short circuit breaking current 31.5kA, mechanical life 10,000 times, maintenance-free structure significantly reduces operation and maintenance costs, suitable for substations, industrial and mining distribution and wind power/photovoltaic high voltage grid-connected systems, in line with IEC 62271 and GB standards
  • Category:
    Outdoor High Voltage Vacuum Circuit Breaker
  • Browse number:
    46
  • Release time:
    2024-10-22 05:11:16
  • Share:
  • INQUIRY

Overview

LW36-126 outdoor high-voltage sulfur hexafluoride circuit breaker is a three-phase AC 50HZ outdoor High-voltage Switchgear, suitable for control and protection of 126KV power transmission and transformation system; it can also be used in the occasions of contact breaking and groups of opening and closing.

LW36-126 type circuit breaker adopts the principle of "thermal expansion + blowing aid" which can only extinguish the arc, and it is equipped with a CTB-1 spring-operated mechanism.

The circuit breaker conforms to GB1984-2003 "AC High Voltage Circuit breakers" and meets the requirements of IEC62271-100:2001 "High voltage switchgear and controlgear - Part 100: High voltage AC Circuit Breakers" of the International Electrotechnical Commission.

  • Main features of circuit breakers:

The circuit breaker adopts the principle of self-energy arc extinguishing, with excellent breaking performance, short arc-burning time, long electrical life and low operating noise. SF6 gas with excellent insulation and arc extinguishing performance is used as the insulation and arc extinguishing medium, with no danger of combustion and explosion, and can be used in densely populated areas. The circuit breaker is equipped with spring actuating mechanism, simple and compact structure, safe and reliable.

  • Environmental conditions of use

1.3.1 Ambient temperature -30 ℃ ~ +40 ℃ (special requirements of -40 ℃ ~ +40 ℃)

1.3.2 Altitude ≤4000m

1.3.3 Air temperature

Relative temperature: daily average not more than 95%

Monthly average not more than 90% (25°C)

Saturation vapor pressure:daily average not more than 2.2×10-3 MPa

1.3.4 Wind pressure not greater than 700 Pa

1.3.5 Ice cover thickness 10 mm

1.3.6 Seismic intensity: Horizontal acceleration: ≤0.3g

 Vertical acceleration: ≤0.15g

1.3.7 Intensity of sunlight: 0.1 W/cm2 (at 0.5 m/s wind speed)

1.3.8 Maximum daily temperature difference of 25°C

1.3.9 Nominal creepage ratio distance: 31mm/kV

1.3.10 No flammable and explosive hazards and

chemical corrosion, violent vibration occasions

  • Main technical parameters

serial numbeItemunit (of measure)Technical Parameters
1rated voltageKV126
2Rated frequencyHz50
3rated currentA3150
4Rated short-circuit breaking currentshort-circuit currentkA31.5
DC component-40%
5Rated short circuit durations4
6Rated short-time withstand currentkA40
7Rated short-circuit closing current (peak)kA100
8Rated peak withstand current100
9Rated 1min frequency withstand voltage (RMS))with respect to ground, between phaseskV230
between contacts265
10Rated lightning impulse withstand voltage (peak)with respect to ground, between phases550
650
115min zero gauge pressure withstand (RMS)between contacts,with respect to ground95
12Rated out-of-step breaking currentkAIeX25%
13Near-area fault opening currentIeX90%,IeX75%
14Rated line charging breaking currentA50
15Rated sequence of operation-O-0.3s-CO-180s-CO
16First open pole factor-1.5
17Closing timems≤100
18Split time30≤t≤45
19breaking time≤60
20Opening and closing time60
21Opening synchronization4
22Closing synchronization5
23Rated SF6 gas pressure (20°C)Mpa0.60
24Annual SF6 gas leakage rate-≤0.5%
25Gas Moisture Contentppm (v/v)≤150
26radio interference levelμV≤2500
27mechanical life spantimes6000
28Quality per breakerkg1400
29Mass of SF6 gas per unit6
30Main circuit resistance per poleμΩ70

1.4.2 Mechanical parameters of circuit breakers and actuators are shown in Table 2.

 

1.4.1 The main technical parameters of the circuit breaker are shown in Table 1.

serial numberItemunit (of measure)digitalRemarks
1Dynamic contact travelmm130+2-3
2Angle Stroke27±2
3Spring Mechanism Stroke1000-3
4Clearance between arm rollers and mechanical cams1.4±0.3Breaker in open state, closing spring energized.
5Distance between closing spring locating nut and locating rod B12~47
6Closing solenoid travel C5.0~5.5Circuit breaker in open state
Trigger and release gap D2.0~2.5
C-D3.0~3.5


7Split solenoid travel F2.8~3.2Circuit breaker in closed state
Trigger and release gap G0.8~1.2

F-G1.6~2.4

1.4.3 Control loop and auxiliary loop parameters in Table 3

serial numberItemunit (of measure)Remarks
1Switching and closing circuit control voltagevDC220DC110
2Switching coil currentA小于2.35.5
3Closing coil currentA23.5
4Energy Storage MotorsSupply VoltageVDC220(110)/AC220
Normal operating voltage range-65%~110%
power (output)W450
Energy storage times≤15
number of revolutions per minuter.p.m750
ampsA3.65.5
5Heater has lighting circuit voltageVAC220
6Heater powerW100

1.4.4 SF6 gas pressure parameters are given in Table 4 (20°C).

serial numberItemunit (of measure)Remarks
1Rated inflation pressureMpa0.6
2Charge Air Alarm Pressure0.55±0.03
3lockout pressure0.50±0.03

 

Product structure and principle

2.1 General structure and principle

The overall structure of this product adopts self-energizing arc extinguishing chamber, each pole is a single column with a single interrupter, referred to as pole. Each circuit breaker consists of three poles, and three poles are installed on the same frame, operated by a spring mechanism, mechanical linkage between the three poles. The upper part of the product is the arc extinguishing chamber ceramic sleeve, the middle part is the pillar ceramic sleeve and frame, the mechanism box is centered and suspended in the lower part of the frame, the mechanism box is equipped with a spring-operated mechanism, the electrical control part, the mechanism's output tie rod is connected with the actuating arm of B. The SF6 gas density controller is installed in the front side of the frame, and both ends of the frame are supported by the pillars.

The control principle is categorized into two schemes: single-split circuit and double-split circuit. Annex III: Electrical Control Schematic and Annex IV: Secondary Wiring Diagrams are for reference and are based on the double-split circuit. The engineering agreement shall prevail, and the corresponding electrical control schematic and secondary wiring diagrams will be supplied randomly.

 

 

1.Single-pole circuit breakers (poles) 2.frames 3. nameplates  4. density controllers

5.gas fills and inspection ports 6. mechanism boxes 7. poles Figure 1 Overall structure of circuit breaker

 

Figure 1 Overall structure of circuit breaker

2.1.1 Single-pole circuit breakers

2.1.1.1 The structure of the single-pole circuit breaker is shown in Figure 2

  1. Packing list - One copy

  2. Electrical control principle diagram, secondary wiring diagram - One copy

  3. Product qualification certificate - One copy

  4. Factory inspection report of the product - One copy

  5. On-site installation inspection test report (see Appendix I, to be filled) - Two copies


Comment

(0)
*Captcha:

ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Address:
*Captcha:

RELATED PRODUCTS

Follow us:

Oil&Gas exploited

Automotive Manufacturing

Transportation & Dlistrlbutlon

Manufacture

Industrial Construction

Green Energy

About US

Contact US

The news

Terms & conditions

Case Studies

Site map

Copyright ? 2024  All Rights Reserved

Back to top