	Product Overview
The ZN63A (VS1) indoor high-voltage vacuum circuit breaker is a three-phase AC 50Hz indoor High-voltage Switchgear with a rated voltage of 7.2-12 kV. It serving as a protection and control unit for power grid equipment and power equipment in industrial and mining enterprises.
The circuit breaker complies with the national standards GB1984-89 "AC High Voltage Circuit breakers", JB3855-96 "3.6-40.5kV Indoor AC High Voltage Vacuum Circuit Breakers", DL403-91 "Technical Conditions for 10-35kV Indoor High voltage vacuum circuit breakers" and relevant international IEC standards, and has reliable interlocking function.
Applications and Installation
The ZN63A (VS1)-12 is designed for use in indoor power distribution systems with a rated voltage of 12kV . Its main function is to protect and control electrical equipment in places like power plants, industrial plants, and substations . It is particularly well-suited for applications that require frequent switching and environments aiming for oil-free and minimal maintenance solutions .
A key feature of this breaker is its installation flexibility. It can be configured as a fixed installation unit or combined with a dedicated advancing mechanism to be used as a withdrawable handcart unit . It is compatible with common switchgear models such as KYN28A-12 (GZS1) center-mounted cabinets and XGN series fixed cabinets .
Key Features and Advantages
- Advanced Vacuum Interrupter: The breaker uses a ceramic vacuum interrupter with copper-chromium contact materials and a longitudinal magnetic field contact structure. This design helps to diffuse the arc effectively, resulting in high breaking capacity and long electrical life .
- Enhanced Insulation Design: Many models feature an insulation barrel made using the APG (Automatic Pressure Gelation) process. With added internal skirts and reinforcing ribs, this design provides a higher insulation level and better resistance to dynamic stability currents. Placing the vacuum interrupter inside the barrel also protects it from damage and contamination .
- Integrated Design and Buffering: The device integrates the circuit breaker and operating mechanism into one unit, making it compact and reliable . A well-designed buffer system ensures no bounce during opening, reducing impact and vibration and contributing to its long mechanical life .
Main technical parameters
| Item | Unit | Data | 
| rated voltage | kV | 12/24/40.5 | 
| Rated frequency | Hz | 50 | 
| Rated 1-minute power frequency withstand voltage (phase to phase, ground to ground, port) | kV | 42/65/95 | 
| Rated lightning impulse withstand voltage (phase to phase, ground to ground, port) | kV | 75/118/125 | 
| Rated operating sequence | O-0.3S-CO-180S-CO | 
| Item | Unit | Circuit breaker model | |||||||||
| C-GIS | |||||||||||
| Rated current | A | 630 | 1250 | 1250 | 1600 | 2000 | 2500 | 1250 | 1600 | 2000 | 2500 | 
| Rated short circuit breaking current | kA | 20/25 | 31.5 | 40 | |||||||
| Rated short-circuit closing current (peak) | kA | 50/63 | 80 | 100 | |||||||
| Rated continuous short-circuit time | s | 4 | 4 | 4 | |||||||
| Rated short-circuit current breaking times | times | 30 | 30 | 30 | |||||||
| mechanical life | times | 10000 | 10000 | 10000 | |||||||
Mechanical characteristic parameters of circuit breaker
| name | Unit | Data | ||
| Contact opening distance | mm | 12kV/9±1;24kV/13±1;40.5kV/18±1 | ||
| Overtravel | 3.5±0.5 | |||
| Three phase opening and closing at different stages | ms | ≤2 | ||
| Bouncing time of closing contact | ms | 12kV/ ≤ 2; 24kV/ ≤ 2; 40.5kV/≤3 | ||
| Contact pressure of closing contact | N | 20kA | 25kA | 31.5kA | 
| 2000±200 | 2400±200 | 3100±200 | ||
| Average opening speed | m/s | 12kV/0.9~1.3; 24kV/1.1~1.6;40.5kV/1.8±0.2 | ||
| Average closing speed | 12kV/0.4~0.8; 24kV/0.6~1.0;40.5kV/0.8±0.2 | |||
Appearance and installation dimensions of circuit breakers for handcart models


Normal condition
◆ Environmental temperature: not higher than 40 ℃, not lower than -10 ℃ (allowed for storage and transportation at -30 ℃).
◆ Altitude: not exceeding 1000m. (If an increase in altitude is required, the rated insulation level will be correspondingly increased.)
Relative humidity: daily average not exceeding 95%, daily average saturated vapor pressure MPa, monthly average not exceeding 1.8 × 10
Earthquake intensity: not exceeding level 8.
◆ Places without fire, explosion, serious pollution, chemical corrosion, and severe vibration.