產(chǎn)品中心
Home > Product > Indoor High Voltage Vacuum Circuit Breaker > ZN63A (VS1) -12kV Indoor High Voltage Vacuum Circuit Breaker

    ZN63A (VS1) -12kV Indoor High Voltage Vacuum Circuit Breaker

    ZN63A (VS1) indoor high-voltage vacuum circuit breaker is a three-phase AC 50Hz indoor high-voltage switchgear with a rated voltage of 7.2-12kV, available in handcart and fixed types. Can be equipped with a spring mechanism. Used as a protection and control unit for power grid equipment and power equipment in industrial and mining enterprises.
  • Category:
    Indoor High Voltage Vacuum Circuit Breaker
  • Browse number:
    74
  • Release time:
    2024-10-21 23:20:40
  • Share:
  • INQUIRY

Product Overview

The ZN63A (VS1) indoor high-voltage vacuum circuit breaker is a three-phase AC 50Hz indoor High-voltage Switchgear with a rated voltage of 7.2-12 kV. It serving as a protection and control unit for power grid equipment and power equipment in industrial and mining enterprises.

The circuit breaker complies with the national standards GB1984-89 "AC High Voltage Circuit breakers", JB3855-96 "3.6-40.5kV Indoor AC High Voltage Vacuum Circuit Breakers", DL403-91 "Technical Conditions for 10-35kV Indoor High voltage vacuum circuit breakers" and relevant international IEC standards, and has reliable interlocking function.


Applications and Installation

 

The ZN63A (VS1)-12 is designed for use in indoor power distribution systems with a rated voltage of 12kV . Its main function is to protect and control electrical equipment in places like power plants, industrial plants, and substations . It is particularly well-suited for applications that require frequent switching and environments aiming for oil-free and minimal maintenance solutions .

A key feature of this breaker is its installation flexibility. It can be configured as a fixed installation unit or combined with a dedicated advancing mechanism to be used as a withdrawable handcart unit . It is compatible with common switchgear models such as KYN28A-12 (GZS1) center-mounted cabinets and XGN series fixed cabinets .


Key Features and Advantages

 

- Advanced Vacuum Interrupter: The breaker uses a ceramic vacuum interrupter with copper-chromium contact materials and a longitudinal magnetic field contact structure. This design helps to diffuse the arc effectively, resulting in high breaking capacity and long electrical life .

- Enhanced Insulation Design: Many models feature an insulation barrel made using the APG (Automatic Pressure Gelation) process. With added internal skirts and reinforcing ribs, this design provides a higher insulation level and better resistance to dynamic stability currents. Placing the vacuum interrupter inside the barrel also protects it from damage and contamination .

- Integrated Design and Buffering: The device integrates the circuit breaker and operating mechanism into one unit, making it compact and reliable . A well-designed buffer system ensures no bounce during opening, reducing impact and vibration and contributing to its long mechanical life .


Main technical parameters


ItemUnitData
rated voltagekV12/24/40.5
Rated frequencyHz50
Rated 1-minute power frequency withstand voltage (phase to phase, ground to ground, port)kV42/65/95
Rated lightning impulse withstand voltage (phase to phase, ground to ground, port)kV75/118/125
Rated operating sequence
O-0.3S-CO-180S-CO


ItemUnitCircuit breaker model
C-GIS
Rated currentA630125012501600200025001250160020002500
Rated short circuit breaking currentkA20/2531.540
Rated short-circuit closing current (peak)kA50/6380100
Rated continuous short-circuit times444
Rated short-circuit current breaking timestimes303030
mechanical lifetimes100001000010000


Mechanical characteristic parameters of circuit breaker


nameUnitData
Contact opening distancemm12kV/9±1;24kV/13±1;40.5kV/18±1
Overtravel3.5±0.5
Three phase opening and closing at different stagesms≤2
Bouncing time of closing contactms12kV/ ≤ 2; 24kV/ ≤ 2; 40.5kV/≤3
Contact pressure of closing contactN20kA25kA31.5kA
2000±2002400±2003100±200
Average opening speedm/s12kV/0.9~1.3; 24kV/1.1~1.6;40.5kV/1.8±0.2
Average closing speed12kV/0.4~0.8; 24kV/0.6~1.0;40.5kV/0.8±0.2


Appearance and installation dimensions of circuit breakers for handcart models

61742036f4ed86204a80cd187c160fcd.png

d33180ba-e701-4fed-ace9-50eccc11e545.png


Normal condition

◆ Environmental temperature: not higher than 40 ℃, not lower than -10 ℃ (allowed for storage and transportation at -30 ℃).

◆ Altitude: not exceeding 1000m. (If an increase in altitude is required, the rated insulation level will be correspondingly increased.)

Relative humidity: daily average not exceeding 95%, daily average saturated vapor pressure MPa, monthly average not exceeding 1.8 × 10

Earthquake intensity: not exceeding level 8.

◆ Places without fire, explosion, serious pollution, chemical corrosion, and severe vibration.


Factory photos

17b2bd96401a0ec7e004fd42374cc0a.pngf09469a217af61804f0274c0c770f8a.png


Comment

(0)
*Captcha:

ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Address:
*Captcha:

RELATED PRODUCTS

Follow us:

Oil&Gas exploited

Automotive Manufacturing

Transportation & Dlistrlbutlon

Manufacture

Industrial Construction

Green Energy

About US

Contact US

The news

Terms & conditions

Case Studies

Site map

Copyright ? 2024  All Rights Reserved

Back to top